S7 Writer Documentation
Version: 1.3.0
Retrieved:Â 2025-10-09 15:16:15
S7 Writer
Used for writing values to Siemens S7 PLC´s. The module will write values to the PLC when a message is received from a previous module and then pass the result to the next module(s) in the flow.
Compatible with S7-200, S7-300, S7-400, S7-1200, S7-1500
Note
To write data to S7-1200 and S7-1500 PLC´s the following settings must be used on the PLC
- "Optimized block access" must be disabled for the DBs you want to access
- "Permit access with PUT/GET" must be enabled
Settings
| Name | Requirements | Purpose | Default |
|---|---|---|---|
| IP Address | String with length 1 to 39 | IP Address of the PLC to use. | `` |
| Port | Number 1 to 65000 | Port of the PLC to use | 102 |
| Rack | Number 0 to Int.Max | Index of Rack to use | 0 |
| Slot | Number 0 to Int.Max | Index of Slot to use | 0 |
| CPU Type | Â | The S7 CPU Type to connect to | S71200 |
| Source Property | String with length 1 to 64 | The property that contains the value to write to the PLC | data |
| Use Tag Specification from Message | Boolean | If not checked the Tag Specification have to be set in settings | false |
| Tag Specification | See below | Â | Â |
Tag Specification
The data types for the properties on the tag object are:
| Name | Requirements |
|---|---|
| s7DataArea | One of (Input, Output, Memory, DataBlock) |
| s7DbAddress | number 0 - 10000 |
| s7StartAddress | number 0 - 10000 |
| s7BitAddress | number 0 - 7 |
| s7Type | One of (Bool, Byte, Word, DWord, Char, SInt, Int, DInt, USInt, UInt, UDInt, Real, LReal, String, DateTime) |
Examples
Example with passing only value on input message
# Settings:
IP Address = 192.168.2.15
Port = 102
Rack = 0
Slot = 0
CPU Type = S71200
Source Property = data
Use Tag Specification from Message = false
Tag Specification:
S7DataArea = DataBlock
S7DbAddress = 1
S7StartAddress = 0
S7BitAddress = 0
S7Type = Bool
# Incoming message:
{
data : true
}
# Outgoing message:
{
data : true,
crosser : {
success : true
}
}
Example with passing value and Tag Specification on input message
# Settings:
IP Address = 192.168.2.15
Port = 102
Rack = 0
Slot = 0
CPU Type = S71200
Source Property = data
Use Tag Specification from Message = true
# Incoming message:
{
data : true,
s7DataArea = 'DataBlock'
s7DbAddress = 1
s7StartAddress = 0
s7BitAddress = 0
s7Type = 'Bool'
}
# Outgoing message:
{
data : true,
s7DataArea = 'DataBlock'
s7DbAddress = 1
s7StartAddress = 0
s7BitAddress = 0
s7Type = 'Bool'
crosser : {
success : true
}
}
Output
Output will be the same as the input including a crosser object that reports if the operation was a success or not.
Search Documentation
Industrial